Model No. : SC10-6(10) (IV)
Brand Name :

Product description

  • Product Details

Basic Specification

Phase number 3
Rated primary voltage 6 up to 10 kV
Installed place Indoor
Vector group 18 Yyn0 or Dyn11
Colour Red
Frequency Medium Frequency
Ratio-voltage Other
Application Current, Instrument, Potential, Power, Reactor
Coil Number Other
Phase Three
Efficiency 95
Zone Of Application Russia
Coil Structure Toroidal

Detail Description

 Product Name: Three Phases Cast Coil  Dry Type Power Transformer

 

  1. Application

1). Our power transformers are especially suitable for installation in draw-out type or fixing type switchgears as well as for power plants, substation, self-consumption transformers, power distribution, transmitter system, earthing system, community power supply system, subway, or those places where small space, fire-control, moisture-proof, are needed. Those up to 10kV can be installed in 650 ~ 1200 mm wide switchgear, up to 20kV in a 1000mm wide switchgear and 35kV in 1400 ~ 1600 mm wide switchgear.
2).Our series reactors are suitable for a power system of 6~10kV.They are connected serially with high voltage parallel capacitor group to depress a wave deformation in the system.

  1. Technical Parameters

i) For Power Transformer:
1).Rated Primary Voltage: 6kV up to 35kV
2).Rated Secondary Voltage: 0.4kV
3).Rated Capacity: 3kVA up to 2500kVA
4).Rated Short-time P. F. Withstand Voltage (r.m.s.) (kV): 20, 25, 35, 50, 70
5).Rated Lightning Impulse Withstand Voltage (Peak) (kV): 60, 75, 125, 170
6).Phase No.: single phase or three phases
7).The Highest Temperature Rise of Windings: 100K
8).Insulation Class: F
9).Cooling Mode: AN or FN
10).Enclosure Protection: IP00, IP20 or custom specified
11).Connection Symbol: Yyn0, Dyn11or II0 or custom specified
12).HV Tapping Range (%): ±5 or ±2×2.5
ii) For Series Reactor
1).System Rated Voltage (kV): 3kV up to 35kV
2).Rated Capacity: up to 1200 kVar
3).Rated Current: up to 4000A
4).Rated Voltage For Capacitor (kV): 6.6√3, 7.2√3, 11√3, 12√3
5).Rated Frequency: 50Hz (60Hz on request)
6).Installation: indoor or outdoor
7).Series Reactor Number for Each Phase: 1
8).Insulation Class: F
* Except for the technical parameters list above, we can design as per clients’ requirements.

  1. Main Features

1).Low partial discharge  
2).Protection against short circuit
3).High mechanical strength  
4).Pre-galvanized steel frame, flame-resistant, against corrosion
5).Long lifespan
6).Cast epoxy resin in vacuum process

  1. Materials

1).Insulation Material: epoxy resin
2).Winding Material: Aluminum wire or high quality enameled copper wire (foil winding is available for power transformer)
3).Core: core lamination, low loss, cold rolled grain oriented silicon steel
5. Types of Our Reactors:
  1).Dry-type Air Core Reactors, including: Dry-type Air Core Series Reactors, Dry-type Air Core Current Limiting Reactors and Dry-type Air Core Shunt Reactors.
  2).Core-type Reactors, including: Core-type Series Reactors, Core-type Start-up Reactors, Core-type Shunt Reactors, Arc Suppression Coils, Core-type Earthing Transformer and Filter Reactors and so on.
6. Manufacturing Standard
1) Power transformer: IEC60076-11:2004, GB1094.11-2007, GB/T10228-2008
2) Series reactor: IEC60076-6:2007, GB/T 1094.6-201
7. Minimum Oder: 1 unit, delivery time: 6 days
8. Production Capability: 20,000 pieces per year.



6.This products is especially suitable to be mounted in the movable or firm switch cabinet,whose width is 650-1200mm. SC10-6(10) (IV) is small,fire-proof and wet-proof.

7.The highest temperature rise of the products’ windings is 100K, their insulation class is F class, and their cooling mode is AN.

8.Technical Parameters for SC10-6(10) (IV) Power Transformers please see Table 1~2

Table 1
 

Rated Voltage
(kV)
Rated Short-time Power Frequency Withstand Voltage (r.m.s.)
(kV)
Rated Lightning Impulse Withstand Voltage (peak)
(kV)
Remarks
6 20
25
60 Declare clearly the withstand voltage in the parenthesis if needed while ordering, otherwise the product of 20kV withstand voltage will be supplied.
10 35 75
 

 

Table 2
 

Model Rated Capacity
(kVA)
Voltage Combination Connection Symbol* No-load Loss
(W)
Load Loss
(W)
(120°C)
No-load Current
(%)
Impedance
(%)
HV
(kV)
HV Tapping Range (%) LV
(kV)
SC10-30/10 30 6
6.3
10
10.5
11
±5
±2×2.5
0.4 Yyn0
Dyn11
190 710 2.1 4
SC10-50/10 50 270 1000 2.1
SC10-80/10 80 370 1380 1.6
SC10-100/10 100 400 1570 1.6
SC10-125/10 125 470 1850 1.4
SC10-160/10 160 540 2130 1.4
 

 

Additional Information

Payment Terms L/C, T/T
Minimum Order 1 unit
Lead Time / Delivery Time 10 Day(s)
Sample Available YES
Delivery Details Delivery Time: Low voltage products: 5-10 days.Medium voltage products: 15-20 days.High voltage products: 30-45 days.
FOB Port Guangzhou
Loading Info We have our own transportation department. Goods can be Loaded whenever they are ready.And delivered to the Guangzhou Port or Airport nearby.
Packing Info Goods are packed in wooden cases, with foam inside for protection.And we have a team who is in charge of packing, including packing design..These enable our packing reasonable。