30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA
30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA
30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA
30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA
30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA

1 / 3

30-2500kVA Cast Coil Foil Winding Power Transformer 30kVA

Get Latest Price
Send Inquiry
Model No. : SC(B)10
Brand Name :

Product description

  • Product Details

Basic Specification

Isulation material epoxy resin
Ratd primary voltage 6-11kV
Application power distribution
Low voltage 0.4kV
Rated capacity 30 up to 2500 KVA
Power Distribution Equipment Application voltage step down
Power Distribution Equipment Surface Treatment galvanized
Application Other
Surface Treatment Other

Detail Description



 

  1. Application

1). Our power transformers are especially suitable for installation in draw-out type or fixing type switchgears as well as for power plants, substation, self-consumption transformers, power distribution, transmitter system, earthing system, community power supply system, subway, or those places where small space, fire-control, moisture-proof, are needed. Those up to 10kV can be installed in 650 ~ 1200 mm wide switchgear, up to 20kV in a 1000mm wide switchgear and 35kV in 1400 ~ 1600 mm wide switchgear.
2).Our series reactors are suitable for a power system of 6~10kV.They are connected serially with high voltage parallel capacitor group to depress a wave deformation in the system.

  1. Technical Parameters

i) For Power Transformer:
1).Rated Primary Voltage: 6kV up to 35kV
2).Rated Secondary Voltage: 0.4kV
3).Rated Capacity: 3kVA up to 2500kVA
4).Rated Short-time P. F. Withstand Voltage (r.m.s.) (kV): 20, 25, 35, 50, 70
5).Rated Lightning Impulse Withstand Voltage (Peak) (kV): 60, 75, 125, 170
6).Phase No.: single phase or three phases
7).The Highest Temperature Rise of Windings: 100K
8).Insulation Class: F
9).Cooling Mode: AN or FN
10).Enclosure Protection: IP00, IP20 or custom specified
11).Connection Symbol: Yyn0, Dyn11or II0 or custom specified
12).HV Tapping Range (%): ±5 or ±2×2.5
ii) For Series Reactor
1).System Rated Voltage (kV): 3kV up to 35kV
2).Rated Capacity: up to 1200 kVar
3).Rated Current: up to 4000A
4).Rated Voltage For Capacitor (kV): 6.6√3, 7.2√3, 11√3, 12√3
5).Rated Frequency: 50Hz (60Hz on request)
6).Installation: indoor or outdoor
7).Series Reactor Number for Each Phase: 1
8).Insulation Class: F
* Except for the technical parameters list above, we can design as per clients’ requirements.

  1. Main Features

1).Low partial discharge  
2).Protection against short circuit
3).High mechanical strength  
4).Pre-galvanized steel frame, flame-resistant, against corrosion
5).Long lifespan
6).Cast epoxy resin in vacuum process

  1. Materials

1).Insulation Material: epoxy resin
2).Winding Material: Aluminum wire or high quality enameled copper wire (foil winding is available for power transformer)
3).Core: core lamination, low loss, cold rolled grain oriented silicon steel
5. Types of Our Reactors:
  1).Dry-type Air Core Reactors, including: Dry-type Air Core Series Reactors, Dry-type Air Core Current Limiting Reactors and Dry-type Air Core Shunt Reactors.
  2).Core-type Reactors, including: Core-type Series Reactors, Core-type Start-up Reactors, Core-type Shunt Reactors, Arc Suppression Coils, Core-type Earthing Transformer and Filter Reactors and so on.
6. Manufacturing Standard
1) Power transformer: IEC60076-11:2004, GB1094.11-2007, GB/T10228-2008
2) Series reactor: IEC60076-6:2007, GB/T 1094.6-201
7. Minimum Oder: 1 unit, delivery time: 6 days
8. Production Capability: 20,000 pieces per year.

 

Technical Parameters for SCB Power Transformers please see Table 1~2:

Table 1

Table 2

Rated
Power
(kVA)
Voltage Combination Connection
Symbol
SCB9 SCB10 No-load
Current
(%)
Impedance
(%)
Secondary
Terminals
Primary
(kV)
HV Tapping
Range
(%)
Secondary
(kV)
No-load
Loss
(W)

 
Load Loss
(W)
(120℃)
No-load
Loss
(W)
Load Loss
(W)
(120℃)
30 6
6.3
6.6
10
10.5
11
±5
or
±2×2.5
0.4 Yyn0
or
Dyn11
220 750 190 710 2.1 4 -
50 310 1060 270 1000 2.1 -
80 420 1460 370 1380 1.6 -
100 450 1670 400 1570 1.6 -
125 530 1960 470 1850 1.4 -
160 610 1460 540 2130 1.4 -
200 700 2250 620 2530 1.0 -
250 810 2680 720 2760 1.0 -
315 990 2920 880 3470 1.0 -
400 1100 3670 980 3990 0.9 -
500 1310 4220 1160 4880 0.9 (b)
630 1510 5170 1340 5880 0.9 (c)
630 1460 6220 1300 5960 0.9 (d)
800 1710 6310 1520 6960 0.9 6 (d)
1000 1990 7360 1770 8130 0.9 (e)
1250 2350 8610 2090 9690 0.9 (f)
1600 2760 10260 2450 11730 0.9 (f)
2000 3400 15300 3050 14450 0.7 (g)
2500 4000 18180 3600 17170 0.7 (c)

Notes: Detailed technical data and outline drawing are provided upon request.

 

 

Additional Information

Payment Terms L/C, T/T
Minimum Order 1 unit
Lead Time / Delivery Time 15 Day(s)
Sample Available YES
Delivery Details Delivery time:Low voltage products: 5-10 days.Medium voltage products: 15-20 days.High voltage products: 30-45 days.
FOB Port Guangzhou
Loading Info Goods are always delivered on time. We have our own transportation department. Goods can be delivered whenever they are ready.We promise it will be fast and correct!
Packing Info Goods are packed in wooden cases, with foam inside for protection.And we have a team who is in charge of packing, including packing design. These enable our packing reasonable, safe .
Target Market(s) North America, Oceania, Southeast Asia, Eastern Europe, Africa(except Middle East), Hong Kong/ Macao/ Taiwan, Latin America, Japan & Korea, Mainland China, Western & Southern Europe, Northern Europe, Central & Southern Asia, Middle East
Send Inquiry

Product Alert

Subscribe to your interested keywords. We will send freely the latest and hottest products to your Inbox. Don't miss any trade information.

版权所有 © 宁波全贸信息技术有限公司 浙ICP备12012821号-1 浙B2-20200628