Video
1 / 3
Model No. : | RTU12~RTU300 |
---|---|
Brand Name : | Amrta or OEM |
Type : | Air-Cooled |
Jinan, Shandong, China
Product description
Tropical Rooftop Packaged Unit are suited to high static pressure applications where large volume spaces are to be air conditioned. Long pipe and duct runs are possible enabling greater installation flexibility. Operation range of outdoor temperature is from -10℃ to 45℃. And if T3 tropical design, the highest outdoor temperature could be 55 ℃. R410A and R134A is suitable for the high ambient temperature. This Type Rooftop Packaged Commercial Air Conditioner is usually cooling only Type.
● Industrial buildings and logistic centers
● Wide choice of communication interfaces
Technical Data
Model |
RTU45 |
RTU50 |
RTU60 |
RTU75 |
RTU90 |
RTU105 |
||
Cooling capacity |
kW |
44.5 |
50 |
60 |
70 |
90 |
105 |
|
Heating capacity |
kW |
48.7 |
54.3 |
64 |
75.4 |
96.2 |
113.2 |
|
Power supply |
380V / 3Ph / 50HZA |
|||||||
Cooling power input |
kW |
17 |
19.5 |
22.8 |
26.7 |
32.9 |
39.7 |
|
Heating power input |
kW |
15.6 |
18 |
21 |
24.8 |
30.4 |
36.7 |
|
Start current |
A |
168 |
186 |
175 |
199 |
197 |
266 |
|
Working current in cooling |
A |
31.7 |
35.6 |
39.9 |
48.3 |
61 |
70.6 |
|
Working current in heating |
A |
29.9 |
33.5 |
37.5 |
45.4 |
57.3 |
66.3 |
|
Throttle methods |
Thermal expansion valve |
|||||||
Circuits |
2 |
2 |
2 |
2 |
3 |
3 |
||
Refrigerant |
R410A |
|||||||
Compressor |
Type |
Scroll type 380V / 3Ph / 50HZA |
||||||
Qty |
2 |
2 |
2 |
2 |
3 |
3 |
||
Condenser side |
||||||||
Condenser |
Type |
Al+copper tube |
||||||
Axial fan |
Qty |
1 |
1 |
1 |
1 |
2 |
2 |
|
Drive |
Direct drive |
|||||||
Motor power |
kW |
0.25 |
0.37 |
0.37 |
0.55 |
0.75 |
0.75 |
|
Air flow |
m3 /h |
4600 |
7800 |
7800 |
9000 |
12600 |
12600 |
|
Evaporator side |
||||||||
Evaporator |
Type |
Al+copper tube |
||||||
Centrifugal fan |
Qty |
1 |
1 |
1 |
1 |
1 |
1 |
|
Motor power |
kW |
3 |
3 |
4 |
4 |
5.5 |
5.5 |
|
Air flow |
m3 /h |
7600 |
8500 |
10900 |
12500 |
16000 |
19500 |
|
Drive |
Direct drive |
Belt drive |
||||||
External static pressure(Pa) |
250 |
250 |
300 |
300 |
300 |
300 |
||
Filter |
Aluminum frame filter G3 |
|||||||
Noise level dB(A) |
73 |
73 |
73 |
75 |
74 |
75 |
||
Dimension |
L |
mm |
2268 |
2268 |
2298 |
2298 |
2878 |
2878 |
W |
mm |
1440 |
1440 |
1650 |
1650 |
2140 |
2270 |
|
H |
mm |
1167 |
1167 |
1400 |
1400 |
1964 |
1964 |
|
Weight |
kg |
750 |
770 |
830 |
860 |
1160 |
1350 |
* Performance values refer to the following conditions:
Cooling: room air temperature 27.0°C DB RH 50%, ambient air temperature 35°C;
Heating: room air temperature 20.0°C DB, ambient air temperature 7°C DB / 6°C WB.
** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high fan speed.
Delivery Pictures
Video
Jinan, Shandong, China
Send your inquiry to this supplier