Specifications 1.Without SF6 apply;
2.The degree of protection for unit is IP67;
3.Module switch units;
The newest RMUs instead of SF6 RMUs.
Electrical Equipment Ring Main Units Brief Introduction Solid Dielectric Ring Main Unit adopted Epoxy Resin as the insulating material, is a new developed environmental friendly and high-tech product experiencing two years and seven months researching and development with the assistance of related national departments. Solid insulated Ring Main Units adopts insulation technology shielded with Epoxy resin and silicon rubbers. Compact, Light Weight, Reliable and Secured Environmental Friendly International Invention, Domestic Initiative Design Domestic emphasized new product Beijing Initiative product Beijing Torch plan Dimension
CSG | A | B | C |
1 Loop | 440 | 340 | 440 |
2 Loop | 840 | 740 | 840 |
3 Loop | 1240 | 1140 | 1240 |
4 Loop | 1640 | 1540 | 1640 |
5 Loop | 2040 | 1940 | 2040 |
Structure Features All energized parts are sealed into epoxy resin bushing and rubber shield bus bar, fully shield and insulated. Three position load switch structure design Visible switch working position Maintenance-free, suitability for outdoor application Optional Spring operating mechanism, permanent magnetic controller Standard modular design of manual and automatic operating mechanism, flexible assemble enabling Arc-protection by separate phase to phase insulation Comprehensive Modular Design, high standardized modular design enables flexible assembling and maintenance Multiple interlock function, safe operation ensured Equipped with power network automation terminal modular, suitable for enterprises power network updating and rebuilding Operation Mechanism adopts three protection processes, suitable for sever ambient conditions of site Benefits of Product Application Suitability for application in areas with low temperatures The design of solid ring main unit reduces the dependence on SF6 gas which eliminate the potential problem caused by insulation gas of being liquefied under low temperature Suitability for application in areas with high temperatures The increased pressure caused by higher temperature is no longer an issue for solid dielectric ring main unit Suitability for application in low-lying areas and construction sites with labor forces The density of SF6 is five times more than normal air under the same condition, leaked SF6 are easily deposited in low-lying areas which is very dangerous for people working there. People can be suffocated by leaked gas. Suitability for application in closed environment: Vacuum arc extinguishing chamber is under normal pressure where all bushing and sealed fillings are solid dielectric which prevent the potential of explosion caused by normal gas insulated product. Suitability for frequent switching operation SF6 load switch is designed for switch operations for up to 2000 times, while the switch operations for solid dielectric designed ring main units are more than 100000 times. Suitability for environmental protection The green house effect caused by SF6 has drawn much attention, solid dielectric designed ring main unit eliminate the use of SF6 gas, which further meet the national requirement for environmental protection. Specification
| Modular C | Modular F | Modular B |
Fuse Switch | composite apparatus | Vacuum Circuit Breaker | Isolating/earth Switch |
Rated Voltage kV | 12 | 12 | 12 | 12 |
Power frequency withstand voltage, Phase to phase, phase to earth/phase to breaking point kV | 42/42 | 42/42 | 42/42 | 42/48 |
Lighting Impulse Withstand voltage,Phase to phase, phase to earth/phase to breaking point kV | 75/95 | 75/95 | 75/95 | 75/95 |
Rated Current A | 630 | 125 | 630 | |
Closing loop breaking current A | 630 | 125 | 630 | |
Cable charging breaking current A | 10 | | | |
5% Overload Breaking current 5% | 31.5 | | | |
Earth fault cable charging breaking current A | 31.5 | | | |
Earth fault cable charging breaking current | 17.3 | | | |
Short-circuit breaking current kA | | P.S | 20 | |
Closing capacity | 50 | P.S | 50 | 50 |
Short time withstand current 4 S | 20 | 20 | 20 | |
Rated transferring current | | 1500 | | |