Residual Current Operated MCCB YCM1LE timer circuit breaker General YCM1LE series residual Current Circuit Breaker(herein after called circuit breaker)is applied for the power distribution network of AC 50Hz,rated current 800A.The circuit breaker can protect people against indirect contact with dangerous electric current and prevent fire disaster caused by insulation fault and single-phase ground fault.It can be used to distribute electric power and protect power equipment against overload and short circuit.The circuit breaker can change the circuit and start motor infrequently.The rated residual operating current and the maximum off-time can be adjusted on-site according to actual situation,the circuit breaker can be customized alarm function and no tripping function. The YCM1LE complies with standard of IEC60947-2, GB14048.2. Main parts: main switch (including current release), zero-sequence transformer, electronic amplify parts, residual release. Related products MCCB YCM1 YCM2 YCM3 YCM6 YCM7 ELCB YCM1LE YCM3LE YCM7LE YCM9LE Type designation
Specifications
Type | YCM1LE-100 | YCM1LE-225 | YCM1LE-400 | YCM1LE-630-800 |
Frame current Inm(A) | 100 | 225 | 400 | 630, 800 |
Rated current In(A) | 10, 16, 20, 25, 32, 40 50, 63, 80, 100 | 100, 125, 140, 160 180, 200, 225 | 225, 315, 350, 400 | 400, 500, 630 700, 800 |
Pole | 2 | 3 | 4 | 2 | 3 | 4 | 3 4 | 3 4 |
Rated insulation voltage Ui(V) | AC800 |
Rated working voltage Ue(V) | AC400 |
Rated impulse withstand voltage Uimp(V) | 8000 |
Arcing-over distance (mm) | 50 | 100 |
Breaking ability level | L | M | H | L | M | H | L | M | H | L | M | H |
Rated ultimate short-circuit breaking capacity Icu(kA) | 30 | 50 | 85 | 30 | 50 | 85 | 50 | 65 | 100 | 50 | 65 | 100 |
Rated working short-circuit breaking capacity Ics(kA) | 15 | 35 | 50 | 15 | 35 | 50 | 35 | 42 | 65 | 35 | 42 | 65 |
Rated residual short-circuit breaking capacity | 7.5 | 13 | 21 | 7.5 | 12.5 | 21 | 12.5 | 13.5 | 25 | 12.5 | 13.5 | 25 |
Rated residual operating current IΔn(mA) | No time-delay type | 30/100/500 100/300/500 | 30/100/500 100/300/500 | 100/300/500 | 300/500/1000 |
Time-delay type | 100/300/500 | 100/300/500 | 100/300/500 | 300/500/1000 |
Rated residual unoperating current IΔn(mA) | | 1/2 Iδn | 1/2 Iδn | 1/2 Iδn | 1/2 Iδn |
Operating performance (times) | Power on | 1500 | 1000 | 1000 | 1000 |
Power off | 8500 | 7000 | 4000 | 4000 |
Total times | 10000 | 8000 | 5000 | 5000 |
Residual current protection opreating time | | Iδn | 2IΔn | 5IΔn | 10IΔn |
Max. breaking time(s) | No time-delay type | 0.2 | 0.1 | 0.04 | 0.04 |
Time-delay type | 0.4/1 | 0.4/1 | 0.3/1 | 0.3/1 |
Overall and Installation Dimension
Pictures
WHY US?
1. We Are Suppler of Three Gorges Project,China National Petroleum,Sinopec Group;
2. China Famous Export Enterprise, Our Products Sale in Over 100 Countries;
3. Our Laboratory is China Key Industrial Electrical Laboratory;
4. We have completely sales service system, ensure every detail is going smooth.
5. We have new designed products each year by our R&D Dpartment.
6. Perfect testing system ensure each product is qualified. 7. Want know more of us? Waiting for your inquiry.
timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker timer circuit breaker