Model No. : HLC-34VE
Brand Name : GOLDEN

Product description

HVAC Concealed Vertical Fan Coil Units / Hydronic Fan Coil Unit

Specifications:

Model-HLC~

34VE

51VE

68VE

85VE

102VE

136VE

170VE

204VE

238VE

Air flow
(m3/h)

High speed

340

510

680

850

1020

1360

1700

2040

2380

Medium speed

255

383

510

638

765

1020

1275

1530

1785

Low speed

170

255

340

425

510

680

850

1020

1190

Cooling capacity

High

W

2247

3146

4146

5056

5955

7758

9657

11601

13965

BTU

7669

10737

14150

17256

20324

26478

32959

39594

47663

Medium

W

1620

2440

3290

4120

4850

6550

8190

9730

11580

BTU

5529

8328

11229

14062

16553

22355

27952

33208

39523

Low

W

1310

2010

2650

3320

3900

5300

6610

7860

9350

BTU

4471

6860

9044

11331

13311

18089

22560

26826

31912

Heating capacity

High

W

3251

4697

6189

7747

9491

11997

14732

18162

22137

BTU

11096

16031

21123

26441

32393

40946

50280

61987

75554

Medium

W

2350

3520

4530

6040

6850

9260

11740

14140

16360

BTU

8021

12014

15461

20615

23379

31604

40069

48260

55837

Low

W

1620

2470

3130

4170

4740

6500

8180

9710

11290

BTU

5529

8430

10683

14232

16178

22185

27918

33140

38533

Surplus pressure
of outlet (Pa)

Normal

0 or 12

High static pressure

30 or 50

Cooling water temperature

7-12℃

Hot water temperature

40-60℃

Power supply

AC220V/50Hz

Heat Exchanger

Type

copper pipes covered into aluminum fins, fin pitch 2.2mm

Water supply kg/h

324

482

655

814

936

1278

1602

1915

2178

Water resistance kPa

30

30

30

30

40

40

40

40

50

Working pressure

1.6MPa

Low static pressure FCU

Input power w

37

52

62

76

96

134

152

189

228

Motor power w

10

16

20

25

30

20×2

25×2

30×2

40×2

Products Show:

Description:

  1. Low noise.
  2. Easy installation.
  3. Special design of air filter.
  4. Air flows: 340 to 2400m3/h.
  5. Cooling capacity range: 2.8 to 14kW.

  1. Used for:Industry,hotel,commercial bulding,etc.
  2. Function:cooling only,cooling and heating.
  3. Power supply: 220V, 50HP, and 1pH depends on the different country.
  4. Test condition for rated refrigerating output of fan coil unit.

  1. Temperature of dry ball: 27 degree Temperature of wet ball: 19.5 degree Temperature of inlet water: 7 degree Temperature difference between inlet water and outlet water: 5degrree.
  2. Test condition for rated heating output of fan coil unit: Temperature of dry ball: 21 degree Temperature of inlet water: 60 degree Rated water volume is same as in test condition of rated refrigerating output Items marked with refers to single-shaft motor.

Applications:

Wall mounted fan coil unit

Competitive Advantage:

1, Exquisite structure ,pleaseing in appearance ,reasonable product structure ,fir insulation.