1 / 1
Model No. : | DZ30LE, DZ30LE-32 |
---|---|
Brand Name : | CNC or OEM, CNC |
Product description
Type | Test current | Tripping time | Type | Test current | Tripping time |
B,C | 1.13In | t≥1h(In≤63A) | B | 3In | t≥0.1s |
1.13In | t≥2h(In>63A) | C | 5In | t≥0.1s | |
B,C | 1.45In | t<1h(In≤63A) | |||
1.45In | t63A) | B | 5In | t<0.1s | |
B,C | 2.55In | 1s<t<60s(In≤32A) | C | 10In | t<0.1s |
2.55In | 1s<t<120s(In<32A) |
Standard | IEC/EN 61009-1 | ||
Electrical features | Poles | P | 1P+N |
Type(wave form of the earth leakage sensed) | AC | ||
Thermo-magnetic release characteristic | B, C | ||
Rated current In | A | 6, 10, 16, 20, 25, 32 | |
Rated voltage Ue | V | 230 | |
Rated sensitivity lΔn | A | 0.03, | |
Rated residual making and breaking capacity lΔm | A | 500 | |
Rated short-circuit capacity lcn | A | 3000 | |
Break time under lΔn | s | ≤0.1 | |
Rated frequency | Hz | 50/60 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind.Freq.for 1min | kV | 2 | |
Insulation voltage Ui | V | 250 | |
Pollution degree | 2 | ||
Mechanical features | Electrical life | t | 2000 |
Mechanical life | t | 2000 | |
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Ambient temperature(with daily average≤35°C) | °C | -5~+40 | |
Storage temperature | °C | -25~+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 16 | |
AWG | 18-5 | ||
Terminal size top/bottom for busbar | mm² | 25 | |
AWG | 18-3 | ||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | ||
Connection | From top |