1 / 1
Model No. : | DPNLE(DZ30LE) |
---|---|
Brand Name : | Winston/OEM |
Product description
Number of Poles | 1P+N |
Rated Current (A) | 6, 10, 16, 20, 25, 32 |
Rated Residual Operating Current ()(mA) | 30 |
Rated Residual Non-Operating Current ()(mA) | 15 |
Rated Voltage (V) | 230 |
Residual Current Off-time | ≤0.1S |
Short Circuit Capacity (Icu) | 4500A |
Testing Current(A) | Rated Voltage(V) | Limited Time | Pre-engage Result | Start Situation | Note |
1.13In | all | t≥1h | non-trip | cold state | The current rise steadily to a fixed value within 5s |
1.45In | all | t<1h | trip | heat state | |
2.55In | all | 1s | trip | cole state | Open the supplementary switch, connect the power |
5In | all | t≥0.1s | non-trip | cold state | Open the supplementary switch, connect the power |
10In | all | t<0.1s | trip | cole state | Open the supplementary switch, connect the power |
Send your inquiry to this supplier