Product description
Specifications 10kV XLPE insulated overhead cable
Conform to IEC,BS,ASTM,DIN etc.
ISO 9001 Certificate
Prompt Delivery
Pro.QC/QA system
Cu / XLPE / PVC Cable This product applies to rated voltage of 10KV AC overhead fixed laying. 1. Performance 1.1 Cable soaked in room temperature water (add-electrode), the 18000v withstand voltage test after 1h 1.2 U (Um) 10kV (12) kV overhead cables for single-phase ground fault time, generally not more than 1min for each system can be used for the longest time of not more than 8h, annual aggregate of not more than 125h systems. 2. Use of Properties 2.1. Rated Voltage U (Um) for 10kV (12kV). 2.2. Cable laying temperature should not be less than -20°C 2.3. Short happen (the longest duration is no more than 5s) the maximum temperature of cables 250°C. 2.4. The allowable long-term working temperature of cable conductor: 90°C. 2.5. When installation the minimum allowed bending radius are not less than 20 (D+d) ±5%mm; D-actual diameter of cable; d-actual conductor diameter).