1 / 2
Model No. : | RS-L240WS |
---|---|
Brand Name : | Risingsun or OEM |
Industry Chiller Condition : | New |
Product description
Microcomputer Display Control Water Chillers
Description of the Water Chillers,
1, Water Chillers have the following components to prevent any operational failure: Compressor protection by designed timer, over current relay, compressor motor temperature sensor, anti-freeze temperature controller, sight glass, oil heater, compressor reverse phase protection relay, high and low voltage protection, air exhaust high temperature protection, safety valve, easy-melt plug.
2. The latest asymmetric rotor tooth profile.
3. four levels or no level capacity control system.
4. Built-in differential pressure oil lubrication system.
5. Low vibration, low noise.
Specification of the Water Chillers,
Model
Unit
RS-L240WS
RS-L280WS
RS-L320WS
RS-L360WS
RS-L440WS
Refrigerating Capacity
KW
792
872
980
1198
1380
Kcal/h
681120
749920
842800
1030280
1186800
Input Power
KW
181
196
227
273
308
Control Type
Expansion Valve
Power
3 phase/380V/50HZ(200V/220V/415V 50HZ/60HZ)
Evaporator
Type
Shell and Tube Type
Cooling water flow
m3/h
136
150
168
206
240
Water Page diameter
inch
6"
6"
6"
8"
8"
Refrigerant Type
R22(R407C)
Compressor
Type
Semi-Hermetic Screw
Quantity
2001-2-4
Start up mode
Y-△
Capacity control
%
0-25-50-75-100
Condenser
Type
Shell and Tube Type
Cooling water flow
m3/h
170
186
220
252
294
Water page diameter
inch
4"x2
5"x2
5"x2
6"x2
6"x2
Safty Protection
High and low Pressure Protection,Over Load Protection,Over Temperature Protection,Phase Sequence Protection etc.
Dimensions (L*W*H)
mm
4150*1320 *2150
4250*1320 *2150
4350*1320 *2150
4450*1580 *2230
4900*1600 *2350
Unit Exchange
1KW=860Kcal/h 1RT=3024Kcal/h 1Btu/hr=0.252Kcal/h
Note:
1.Cooling Capacity is calculated based on: inlet/outlet chilled fluid temperature: 12℃/7℃, inlet/outlet cooling water temperature: 30℃/35℃.
2.Working condition: Chilled fluid temperature from 5℃ to35℃, Inlet/outlet chilled fluid Temperature difference from 3℃ to 8℃.
3,Cooling water temperature: from 18℃to 37℃, Inlet/outlet cooling water Temperature difference: from 3.5℃ to 10℃.