Transformer Frequency Response Tester (GDRB-II)
Transformer Frequency Response Tester (GDRB-II)
Transformer Frequency Response Tester (GDRB-II)

1 / 1

Transformer Frequency Response Tester (GDRB-II)

Get Latest Price
Send Inquiry
Model No. : GDRB-II
Brand Name :
10yrs

Dongxihu District, Wuhan, China

Visit The Store

Product description

GDRB-II Transformer Frequency Response Tester detects transformer winding movements and mechanical failures due to mechanical shock, transportation or short circuits. Detection of these displacements ahead of a dielectric failure can reduce unplanned maintenance costs, and provide the possibility to improve system reliability by preventing outages. Additionally, when damage is discovered, repairs may be targeted to a specific phase winding. GDRB-II can detect all level power transformers.
Technical specifications
Operating Temperature: -10...+60degree
Storage Temperature: -20...+70degree
Relative Humidity: 10...90 % non-condensing
Mains Universal: 220± 10% (110+-10%) VAC, 50 / 60 Hz, 100W
Dimensions Instrument: 32cm x 30cm x 12 cm
Weight Instrument: 20 kg
Automatic interpretation according to Chinese standard DL/T911-2004.
Calibration interval: 3 years
Measurement
Source output: One channel
Source frequency range: 10Hz~10MHz
Source Frequency accuracy: 0.01%
Source impedance: 50Ω
Source amplitude: Max. 10Vpeak_peak, user difined
Analog input number: Two channels
Input impedance: 50Ω Or 1MΩ
Sampling: Max 100MHz per channel
Accuracy: 0.5dB at +20dB~-80dB
Dynamic range: +20dB~-80dB
Protection: Against short circuit overload
Measuring Points: Max. 3'000, user defined
Data Display and Data export
Plot: Frequency vs. Magnitude, Impedance, Phase
Sweep mode: Scaling Logarithmic or Linear
Send Inquiry

Product Alert

Subscribe to your interested keywords. We will send freely the latest and hottest products to your Inbox. Don't miss any trade information.

版权所有 © 宁波全贸信息技术有限公司 浙ICP备12012821号-1 浙B2-20200628