Product description
In the power supply system of urban rail transit, three-phase oil-immersed transformers are usually used. The oil immersed transformer mainly consists of iron core, winding, oil tank, voltage regulating device, radiator, oil conservator, gas relay, insulation sleeve, explosion-proof tube, and other parts.
Operating temperature:
Oil immersed transformers can operate according to the nameplate regulations under specified cooling conditions, but the top oil temperature should not exceed 90 ℃. To prevent insulation aging of the transformer, the top oil temperature should generally not exceed 85 ℃ frequently, and the alarm setting should be set at 80 ℃.