1 / 1
Model No. : | GDVA-404 |
---|---|
Brand Name : | Gold |
Apparatus : | Multifunction CT PT Tester |
Product description
Introduction:
Tests for current transformer: | |
1 | Excitation curve and parameters test |
2 | Turns ratio test |
3 | Ratio and phase error test |
4 | Polarity mark check |
5 | Coil resistance measurement |
6 | Secondary loop burden measurement |
7 | Error line curve test for protection CT |
8 | Transient CT parameters test |
9 | CT nameplate guess |
10 | Saturation hysteresis loop curve measurement |
Tests for voltage transformer: | |
1 | Turns ratio test and phase angle error test |
2 | Polarity test |
3 | Secondary burden test |
4 | Coil resistance test |
Applications for CTPT analyzer: | |
1 | CT nameplate check |
2 | CT parameters check in work burden |
3 | CT transient parameters analysis |
4 | CT ratio and phase error calibration |
5 | PT routine test |
CT PT Analyzer Technical Index:
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~180V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Maximum knee voltage measurement | 45kv |
7 | Current measurement | Range:0~10A (automatically change range in 0.1/0.4/2/10A) |
Error <±0.1%+0.01%FS | ||
8 | Voltage measurement | Range:0~200 V (automatically change range in 1V/10V/70V/200V) |
Error < ±0.1%+0.01%FS | ||
9 | Turns ratio measurement | Range :1~35000, |
1~2000 error<0.05% | ||
2000~5000 error>0.1% | ||
5000~35000 error<0.2% | ||
10 | Phase measurement | error:±2min,resolution:0.01min |
11 | Coil resistance measurement | Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) |
Error< 0.2%RDG+0.02%FS | ||
Maximum resolution:0.1mΩ | ||
12 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
13 | CT Secondary burden | Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution 0.001ohm | ||
14 | PT Secondary burden | Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution: 0.1ohm | ||
15 | PT ratio measurement | Range :1~35000, |
1~5000 error<0.2% | ||
5000~35000 error<0.5% | ||
16 | Saved data groups | >1000groups |
17 | Work condition | Temperature:-10°C~50°C, moist:≤90% |
18 | Size | 485mm×356mm×183mm |
19 | Weight | <15Kg |