Iec62271 - 100 40.5kv Vmd5 High Voltage Vacuum Circuit Breaker / Pole Distance 300 ± 1.5
Iec62271 - 100 40.5kv Vmd5 High Voltage Vacuum Circuit Breaker / Pole Distance 300 ± 1.5
Iec62271 - 100 40.5kv Vmd5 High Voltage Vacuum Circuit Breaker / Pole Distance 300 ± 1.5

1 / 1

Iec62271 - 100 40.5kv Vmd5 High Voltage Vacuum Circuit Breaker / Pole Distance 300 ± 1.5

Get Latest Price
Send Inquiry
Model No. :
Brand Name :

Product description

IEC62271 - 100 40.5kv VMD5 High Voltage Vacuum Circuit Breaker / Pole Distance 300 ± 1.5

Technical Parameter

NO

Item

Unit

Technical Date

1

Rated voltage 

kV

40.5

2

Rated short time power frequency withstand voltage(1min)              

95

Raed lighting inpulse withstand voltage (peak value)

185

3

Rated Frequency 

Hz

50/60

4

Rated current 

A

630

630

1250

1250

1250

1600

 

2000

2500

5

Rated short circuit breaking current 

kA

20

25

31.5

6

Rated short time withstand current

20

25

31.5

7

Rated peak withstand current 

50

63

80

8

4S rated short-time withstand current 

20

25

31.5

9

Rated shock steady current 

50

63

80

10

Rated short-circuit closing current (peak value)       

50

63

80

11

Duration of rated short-circuit current

S

4

12

Mechanical life 

Times

10000

13

Rated making surge current of capacitor bank   

kA

12.5 (The frequency 

is less than 1000Hz) 

14

Rated breaking current of single/symmetrical 

capacitor bank 

A

630/400

15

Breaking times at rated short-circuit current     

Times

20

16

Power frequency withstand voltage of 

secondary circuit  

V

2000

17

Rated operating voltage

AC110/220

DC110/220

18

Rated operating order

 

O-0.3s-CO-180s-CO

19

Energy storage times

S

≤15

20

Contactor space 

mm

20 ± 2

21

Contacting travel  

6 ± 1

22

Pole distance

300 ± 1.5

23

Bounce time of Contactor during making         

ms

≤3

24

Different time of breaking / making of 3 phases    

≤2

25

Average breaking speed

m/s

1.5-1.9

26

Average making speed 

0.6-1.3

27

Making time 

ms

30-80

28

Brealing time

20-45

29

Rebound amplitude of contact breaking

mm

≤3

30

Permitted abrasion thickness of moving 

and fixed contacts 

3

31

Conductance circuit resistance 

µΩ

Handcart way   

Rated current            

≤60

under 1250A   

≤60

1600-2000A

≤40

under 2500A    

The average breaking speed refers to the average speed of contactor’s first 12mm,  

and the average making speed is that of contactor’s last 12mm.

 

Outline Dimension Drawing

Dear friens,  pls contact us for the outline dimension drawing,  we will give you quick reply.

Summary

The VMD5 series indoor circuit-breaker is our independent developed new generation 40.5 kv vacuuum circuit breaker.

 Its main characters as follows: the conductance circuit is installed in an three-phase insulating sleeve ,  

its mechanism and conductance circuit adopts front and rear layout. And the mechanism 

is our deveoped new design,  

with simple construction,  reliable operation

 

Technical standard

All the technical parameters of breaker completely satisfy the Standards Of GB1984 

AC Highvoltage Breaker,  

GB/T 11022 -1999 Common Specifications For High-Voltage Switchgear And Controlgear Standards,

 China Power Sector Standards DL403.

Also meet the requirements of IEC62271-100,  IEC56 and other main industrialized countries’ similar standards

 

Testing

VMD5 series circuit breaker have passed has passed following 

test ,  to ensure the product’s safe Operation.

 

Type tests : power-frequency withstand voltage tests ,  lighting impact withstand voltage tests,  ,  temperature rising tests,

 short-time withstand current tests ,  peak withstand current tests , short circuit breaking ability tests ,  

mechanical lift tests, ect

 

Routine test before out of factory: mechanical performance test  ,  power-frequency withstand voltage tests of the main circuit ,  insulating property  tests on control and auxiliary circuits ,

measurement of ther resistance of the main circuit ,  interlock operating tests ,

 mechanical operating tests,  

Electrical Equipment operating tests.

 

Scope of application

 

It is universally used in power plant ,  electric network ,  metallurgy industry petrochemical industry and infrastructures,

such as airport ,  subway,  building.

 

Safety

VMD5 circuit breaker possesses  perfect mechanical and electric interlock equipment ,  meanwhile ,

its high reliable operating performance and mechanical life ,  coodinated with matched switchgear cabinet ,

to ensure normal power distribution ,  operator and equipment’s safety.

 More Information,Please See Our Official Website: www.meletek.com 

Send Inquiry

Product Alert

Subscribe to your interested keywords. We will send freely the latest and hottest products to your Inbox. Don't miss any trade information.

版权所有 © 宁波全贸信息技术有限公司 浙ICP备12012821号-1 浙B2-20200628