Feartures ♦No Moving Parts, Virtually No Pressure Loss; ♦Corrosion protection, abrasion resistant; ♦High accuracy, Stable performance; ♦High level of anti-vibration and anti-jamming, wide measuring dimensions; ♦Multi-Output Interface:4~20mA, Pulse, HART or RS-485,high-low alarm. Specifications
Power | 86~265V AC or 18~36V DC |
Display | 4 line*12 |
Velocity range | 0.01~12m/s |
Sensor range | 3mm~2800mm |
Output | 4-20mA ,pulse, and high-low alarm |
Protocol | HART/RS485/Profibus-DP |
Exciting current | 100mA,125mA,150mA,160mA ,200mA,250mA,300mA,320mA,400mA ,500mA |
Exciting frequency | 3.125HZ,6.25HZ,12.5HZ,25HZ |
High and low alarm | YES/NO |
Empty and full pipe checking | YES |
Electrode checking | YES/NO |
4mA and 20mA calibrate | YES |
Zero point calibrate | YES |
Relay output | YES/NO |
Accuracy | ±0.5% or ±0.25% |
Turndown | >1000:1 |
Operating temprature | -30 to 60℃ (-22 to 140℉) |
IP grade | IP67/IP68 |
Company Flosonic Automation Co.,LTD,focus on industry flow measurement,committed to electromagnetic flow meter and turbine flow meter transmitter’s/converter’s research,development and application.Through long-term cooperation with south Korean FNS PLUS company,Successfully developed converter for magnetic flowmeter,turbine flowmeter,vortex flowmeter,and rotameter. Management culture: Better Flosonic,Best Automation. Contact FLOSONIC AUTOMATION CO.,LTD Add:RM508,Building 1,#89 Huguang East Road,Minhang District,Shanghai,China Tel:+86-21-52967169 Fax:+86-21-52967170 Mob:+86-18116349695 Skype:flosonic.rango Web:www.flosonic.com