1 / 4
Model No. : | EA990 there phase, online UPS 160KVA |
---|
Product description
MODEL | EA99160 | EA99200 | EA99250 | EA99300 | EA99400 | EA99500 |
Capacity | 160KVA 128KW |
200KVA 160KW |
250KVA 200KW |
300KVA 240KW |
400KVA 320KW |
500KVA 400KW |
INPUT | ||||||
Rated Voltage | 380V/400V/415VAC | |||||
Voltage Range | ±15%,starting range ±20%,working range |
|||||
Rated Frequency | 50/60Hz | |||||
Frequency Range | 50/60Hz ±5Hz | |||||
Power Factor | ≥0.99 | |||||
Total Harmonic Distortion (THDi) | ≤5% | |||||
Bypass Voltage Range | ±20% | |||||
ECO Voltage Range | ±10% | |||||
OUTPUT | ||||||
Voltage | 380V/400V/415VAC | |||||
Voltage Regulation | ±1% | |||||
Frequency | Synchronized with utility on AC mode;50/60Hz±0.1% on battery mode | |||||
Waveform | Pure sine wave | |||||
Crest Factor | 3:1 | |||||
Total Harmonic Distortion(THDV) | ≤1%(Linear load);≤5%(Non-linear load) | |||||
Transfer Time | AC mode to battery mode :0ms Inverter model to bypass mode:0ms Inverter model to ECO mode:5-10ms |
|||||
Inverter Overload Capability | 105%-110%:Transfer to bypass after 60mins; 111%-125%:Transfer to bypass after 10mins; 125%-150%:Transfer to bypass after 1mins; 150%-200%:Transfer to bypass after 200 ms; >200%: power off after 100 ms |
|||||
Bypass Overload Capability | ≤150%: Long time running 150%<load<200%: Power off after 1 min >200%:Power off after 100 ms |
|||||
BATTERY | ||||||
DC Voltage | 600V(12V*50pcs) | |||||
Charger Current | 16A | 20A | 25A | 30A | 40A | 50A |
SYSTEM | ||||||
Efficiency | Working mode ≥93%,ECO mode ≥98% | |||||
Alarm | Battery mode, Battery voltage low, Fans fault etc | |||||
Surge Protection | IEC60664-1 | |||||
Insulation Resistance | >2MΩ(500VDC) | |||||
Dielectric Strength | 2820Vdc,No arc in 1min | |||||
IP Class | IP20 | |||||
EMI | EN62040-2 | |||||
EMS | IEC61000-4-2(ESD) | |||||
IEC61000-4-3(RS) | ||||||
IEC61000-4-4(EFT) | ||||||
IEC61000-4-5(Surge) | ||||||
ENVIRONMENT | ||||||
Humidity | 0~95% RH @ 0~40°C(non-condensing) | |||||
Noise Level | 65dB | 70dB | 75dB | |||
MANAGEMENT | ||||||
Communication | RS232,RS485,Dry contact | |||||
Supports Windows 98/2000/2003/XP/Vista/2008/7/8 | ||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||
PHYSICAL | ||||||
Dimension(mm) W*D*H | 1210*860*1950 | 2380*860*1950 | ||||
Packing Dimension(mm) W*D*H | 1300*950*2200 | 1300*950*2200(×2) | ||||
Net/Gross Weight(kg) | 1135/1190 | 1355/1410 | 1790/1900 | 2090/2200 |
Send your inquiry to this supplier