clamp-on current sensor
clamp-on current sensor
clamp-on current sensor

1 / 1

clamp-on current sensor

Get Latest Price
Send Inquiry
Model No. : ME333
Brand Name : PINYAN

Product description

Specifications Output signal is 0.333V

  Flexible Rogowski Coil         FCT is a flexible current probe utilizing the Rogowski principle,which is suitable to conveniently measure single and three phase AC as well as pulsed DC currents. After appropriate signal conditioning, it can be used with digital multimeters, recorders and other suitable equipment to measure current from very low frequencies up to 1MHz.     The probes comprise a flexible air–cored sensor which can be opened, allowing them to be installed around a primary conductor without interrupting the circuit. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas and with large conductors.     Available Models    
Model     Category Advantages
FCT Normal Length is up to 20m. Suitable for metallurgy current detection, the detection of leakage current from the super large equipment to the ground and so on.
FCT-A High accuracy Accuracy up to 0.2%. Excellent anti-disturbance, temperature drift and stability.  
FCT-F Super flexible Suitable for irregular conductor detection, such as the detection of S type output end of transformer
FCT-H High temperature tolerance Temperature tolerance: long time for over 150°, short time for over 200°. Can be used in water or oil.
FCT-M Mini rogowski coil Diameter of the coil is down to 4mm. Suitable for current under 1000A, and application with a limitation of space
FCT-S High sensitivity Output up to 1V/100A. Suitable for leakage/zero-sequence detection, mA level current detection, low-frequency signal (<5Hz) detection
FCT-T Thicker High voltage tolerance. Not easy to deformation. Suitable for high voltage, high temperature, and outdoor application
    Technical  Specification  

 

Basic Frequency

10Hz .. 10kHz Weight of Electronics Approx. 100g
Working Frequency 0.8Hz .. 10MHz Transfer Ratio M 0.05 .. 10 μH
Linearity <0.01% Sensitivity Output voltage Vout=2×π×M×f×IAC 
f=frequency   IAC=current to be measured
Measuring Range
(crest factor<1.5@Basic Frequency)
0.01 .. 300kA Phase Error 90°± 0.1°
Sensor Cable Length 200mm .. 10m
Load Resistance 1kΩ Sensor Cable Diameter 4mm .. 20mm
Operating Temperature -10 .. +60°C Signal Cable Diameter 2.0 .. 5.0mm
Storage Temperature -20 .. +70°C Signal Cable Length 0.1m .. 100m
Output Connection Banana Plug Pair Output Connection
BNC Output Connetion
OEM Cable Output
Calibration Kit
Special Cable Lengths and/or Gains on request
    Ordering Information  
FCT-cate-abc-xyz
cate …… category,refer to available models.       e.g. M=mini rogowski coil
abc …… 3 numbers stand for current range.     e.g. 203=2*103=2000A
xyz …… 3 numbers stand for coil length.           e.g. 600=600mm
       
For example: an FCT-M-203-600 has a current ranges of 2000A and a 600mm circumstance mini rogowski coil.
Custom length, color, sensitivity and other parameters are available.
                 The FCT is an ideal replacement for medium/large current, current transformers(CT’s) and has the advantages that it is:       Suitable to measure currents from mA to hundreds of kA.     Wide dynamic range.     Very useful with awkward shaped conductors or in places with limited available space.     No danger from open-circuited secondary     Not damaged by large overloads     Non-intrusive, no power drawn from the main     Thanks to its light weight, it can be hanged on the measured conductor     Applications   Measuring devices, lab instrumentation DC ripple measurement Analysis of harmonics, power measurements Very high current monitoring Measuring starting transients of electric motors Sudden short circuit testing Protection system for slip-ring induction motors Measuring the currents flowing in the framework of a large generator Shaft Current measurements Measuring the current in Electromagnetic Launchers Monitoring the current in railway lines to check signaling currents Arc furnace currents High-current testing of switch-gear and fuses Measuring leakage currents down insulators   Certification                                                         Typical cases     1. Application to electric furnace       2. Application to high-voltage transmission and distribution   3.  Application to  power quality analysis       Technical Parameters      
Coil length 200mm~10m
Frequency 1HZ~100kHz
Current 50mA~300kA
Accuracy Accuracy of reading (10%~100%F.S.)  Up to 0.3%
Angle deviation  90°±0.2° 
     The signal line of the coil is wear resistant, shielded, coaxial and double layer cable with secure BNC connector. Our rogowski coil supports FLUKE, CA, HIOKI and various brands, and it is the ideal current probe of other related power quality products. Rogowski coil is often used to measure the following parameters: Arms, THDA%f, Aharm, Areac, kW, kVA, kVARQf, kVARD, PF, cosφ(DPF)and so on.                Tel: (86)21-64850006   Fax :(86)21-64850006   Web: http://en.meatrol.cn     Add: unit 66, No.388, Du Shi Road, Min hang District, Shanghai China      