1 / 2
Model No. : | XPC series online ups |
---|---|
Brand Name : | JFY or OEM |
Product description
MODEL | XPC 1106 | XPC 1106L | XPC 1110 | XPC 1110L |
Rated Power | 6KVA/4.8KW | 10KVA/8KW | ||
INPUT | ||||
Phase | L+N+G | |||
Input Voltage | (120±5 to 274±5)Vac | |||
Input Frequency | (46±0.2 to 54±0.2)Hz | |||
Input PF | >0.99 | |||
Bypass voltage | (187±5 to 253±5)Vac | |||
OUTPUT | ||||
Output Voltage | 220Vac±1% | |||
Output Power Factor | 0.8 | |||
Output Frequency | Normal Mode, same with utility power Battery mode: 49.9-50.1Hz | |||
THD | THD<3% (linear load); THD<5% (Non-linear) | |||
Transfer Time | Normal to battery mode: 0ms Bypass mode to normal mode : 0ms | |||
Overload Capability | 105±5%<Load<130±5%: 1min to bypass; 130±5%<Load<150±5%: 30s to bypass; >150±5%: 0.1s to bypass; | |||
BATTERY | ||||
Voltage | 192Vdc | |||
Charging voltage | 220Vdc | |||
Overvoltage | 230Vdc | |||
Charging Current | 2A/4A(L type) | |||
SYSTEM | ||||
Efficiency | >90% | >92% | ||
Communication | RS-232 + Intelligent Slot | |||
Restart Function | After Turning off due to cut off voltage of battery, UPS will restart when voltage is in (175±5~285±5Vac) and frequency is in (47~53Hz). | |||
Noise (1m front) | <45dBA | <50dBA | ||
Operation Temperature | 0°C to 40°C | |||
Humidity | 0~95% non-condensing | |||
Storage Temperature | -40°C to 50°C | |||
Altitude | 1000m | |||
Dimension(W*D*H mm) | 248x500x616 | 240x500x460 | 240x500x615 | 248x500x616 |
Weight(kg) | 57 | 20 | 59 | 21 |
Specification is subject to change without prior notice. |
Send your inquiry to this supplier