XPC series Worldwide adaptable 6kva network ups uninterrupted power supply
XPC series Worldwide adaptable 6kva network ups uninterrupted power supply
XPC series Worldwide adaptable 6kva network ups uninterrupted power supply
XPC series Worldwide adaptable 6kva network ups uninterrupted power supply

1 / 2

XPC series Worldwide adaptable 6kva network ups uninterrupted power supply

Get Latest Price
Send Inquiry
Model No. : XPC series online ups
Brand Name : JFY or OEM

Product description

XPC series Worldwide adaptable 6kva network ups  uninterrupted power supply   1, Features   > True onlin double conversion completely isolates the load from various grid faults and pollution > Digital control technology provides high performance and system reliability. > Advanced IGBT-based the latest rectifier and inverter technology, high input power factor and low output harmonic. > Extra-wide input voltage and frequency range adapts adverse gird environment, compatible with diesel generator. > Intelligent battery management directly checking and setting charge and setting charge and discharge of battery on LCD      extends battery life. > Direct DC cold start function offers emergency on UPS by battery without utility power > Large LCD display monitor various real-time information at a glance. > Multiple monitoring and alarm functions availbale with dry contact of common alarms and RS232 for remote monitoring and      SNMP card(optional) for web-based monitoring     2, Specifications    
MODEL XPC 1106 XPC 1106L XPC 1110 XPC 1110L
Rated Power 6KVA/4.8KW 10KVA/8KW
INPUT
Phase L+N+G
Input Voltage (120±5 to 274±5)Vac
Input Frequency (46±0.2 to 54±0.2)Hz
Input PF >0.99
Bypass voltage (187±5 to 253±5)Vac
OUTPUT
Output Voltage 220Vac±1%
Output Power Factor 0.8
Output Frequency Normal Mode, same with utility power
Battery mode: 49.9-50.1Hz
THD THD<3% (linear load); THD<5% (Non-linear)
Transfer Time Normal to battery mode: 0ms
 Bypass mode to normal mode : 0ms
Overload Capability 105±5%<Load<130±5%: 1min to bypass;
130±5%<Load<150±5%: 30s to bypass;
>150±5%: 0.1s to bypass;
BATTERY
Voltage 192Vdc
Charging voltage 220Vdc
Overvoltage 230Vdc
Charging Current 2A/4A(L type)
SYSTEM
Efficiency >90% >92%
Communication RS-232 + Intelligent Slot
Restart Function After Turning off due to cut off voltage of battery, UPS will restart 
when voltage is in (175±5~285±5Vac) and frequency is in (47~53Hz).
Noise (1m front) <45dBA <50dBA
Operation Temperature 0°C to 40°C
Humidity 0~95% non-condensing
Storage Temperature -40°C to 50°C
Altitude 1000m
Dimension(W*D*H mm) 248x500x616 240x500x460 240x500x615 248x500x616
Weight(kg) 57 20 59 21