1 / 6
Model No. : | JLSZV-12 (W) |
---|---|
Brand Name : | DAELIM |
Product description
Item No. | Picture | Description |
JLSZV-12 (W) Combination Instrument Transformer |
Summary |
The JLSZV-12(W) is combined voltage and current instrument transformers. The product is used in three-phase systems of rated frequency of 50/60Hz and rated voltage of 12kV. The product is alternative to JLSJW-12 oil-immersed combination transformer. |
| Product application
|
The products are provided for metering electric energy, voltage controlling and relay protection. The rated frequency of the electric systems should be 50/60Hz. The products are suitable for outdoor transformer substations in rural areas, as well as for industrial services. It is alternative to JLS-12 oil immersed combination transformer.
|
| Technical specification
|
1. rated voltage: 3×6kV; 3 ×12kV; 3× 35kV 2. accuracy class: 0.5, 0.2, 0.5S and 0.2S 3. rated voltage ratio: 6k/100; 12k/100; 35k/100 4. rated current ratio: 1~1k/5 A (two type: single ratio and double ratio) 5. Primary wiring of double measuring tank: P1, P2 are heavy current ratio while P1, P3 are high current ratio. 6. Rated burden: a) PT components: 15, 25 and 50 VA b) CT components: 10, 25 and 30 VA.
|
| Structure feature |
The transformer is outdoor cast in epoxy resin, fully enclosed and is in supporting type structure. For its special casting technique, the product is excellent in electricity-arc and UV ray resistance, long life expectancy, reliable and cost-efficient. The u nits are composed of two single-phase and fully insulated voltage mutual inductors, which are shaped in V . Two current mutual inductors are respectively connected to phase A or C. And the secondary windings of C T units are tapped for varying current ratios.
The outlet terminal of secondary windings is covered with a protective cover. It is convenient, safe and reliable for connecting, and efficient in prevention of stealing electricity. Four screws on the base plate are designed for fixing purpose. |
Rated primary current | Rated short-time thermal current(KA virtual value) | Rated dynamic current(KA peak value) | Limit output(VA) | |||
0.2 | 0.2S | 0.5 | 0.5S | |||
5-10 | 1.0 | 2.5 | 10 | 15 | ||
10-20 | 1.5 | 3.75 | ||||
15-30 | 2.4 | 6.0 | ||||
20-40 | 3.0 | 7.5 | ||||
30-60 | 4.5 | 11 | ||||
40-75 | 8.0 | 20 | ||||
50-100 | 9.0 | 22.5 | ||||
75-150 | 12 | 30 | ||||
100-200 | 16 | 40 | ||||
150-300 | 24 | 60 | ||||
200-400 | 32 | 80 | ||||
300-600 | 60 | 100 | ||||
400-800 | 80 | 100 | ||||
500-1000 | 80 | 100 |