Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705
Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705
Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705

1 / 1

Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705

$1.00 ~ $1.00 / Set/Sets
Send Inquiry
Model No. : 241115.705
Brand Name : UNIQUE
Usage : Server
Type : Wired
Support Network : GSM
Information content : Data
Certification : CE
Condition : New
More
7yrs

Wuhan, Hubei, China

Visit The Store
  • Platform Certification
  • Online Expo

Product description


Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705.DS3 - v9

 

High efficiency and reliable rectifier/converter

 

The most efficient power conversion module in the industry! Since the launch the Flatpack 2 family has expanded into a wide selection of power ratings and voltages.

The Flatpack2 48-60/2000 HE is a cost efficient rectifier for 48V and 60V lead acid battery systems as well as 48V NiCad.

 

Applications

 

TELECOM

Radio base stations / Cell sites

LTE / 4G / WIMAX

Distributed  Antenna Systems

Microwave / Broadband

Central office

POWER UTILITIES

Control & protection

SCADA

Communications equipment

RAIL & METRO

Control & protection

Signaling

MARINE & OFFSHORE

Communications on ships

 

Key Features

 

High Efficiency –  96.2 %

Proven Reliability

High Power Density

Application Flexibility, 2kW To Multicabinet Installations

Modular Design

Mttr < 5mins

Accepts DC Input (DC/DC Converter)

Global Compliance (CE, Ul, NEBS)

Marine & Offshore Certifications

Patented Technology

 

Specifications

 

Model

48-60/2000 HE

Part number

241115.705

INPUT DATA

 

Voltage (nominal)

185 - 275 VAC  / 185 - 275 VDC

Voltage (operating range)

85 - 300 VAC  / 80 - 300 VDC

Current (maximum) @ nominal input, full load

11.6 ARMS

Frequency

45 - 66 Hz / 0 Hz

Power Factor

> 0.99 at 50% load or more

THD

< 5% at 100% load

Protection

Fuse in L & N, Varistor, Shutdown when input voltage is out of operating range

OUTPUT DATA

 

Voltage (default) 1)

53.5 VDC   (67 VDC  in 60V mode)

Voltage (adjustable range) 1)

39.9 - 72 VDC

Power  (maximum) @ nominal input

2000 W (@VOUT  ≥ 48VDC)

Power @ 85 VAC

750 W

Current (maximum) @ nominal input

41.6 A (@VOUT  < 48VDC)

Hold up time, 1500W output power

>20ms; output voltage > 53.5 VDC  (60V mode)

Current sharing (10 - 100% load)

±5% of maximum current from 10 to 100% load

Static Voltage regulation (10 - 100% load)

±0.5%

Dynamic Voltage regulation

±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms

Ripple & noise

< 150 mVPP , 30 MHz bandwidth / < 2 mVRMS psophometric

Protection

Fuse , Short circuit proof, High temperature protection, Over voltage Shutdown

OTHER SPECIFICATIONS

 

Efficiency

96.2 %

Isolation

3.0 kVAC  - input to output, 1.5 kVAC  - input to earth, 500 VDC  - output to earth

 

Low / high input voltage shutdown, High / low temperature shutdown, Rectifier

Alarms: Red LED

Failure, Overvoltage shutdown on output, Fan failure, Low output voltage

alarm, CAN bus failure

Rectifier in power de-rate mode,  Remote output current limit activated, Input

 

 

Warnings: Yellow LED

voltage out of range, flashing at overvoltage, Loss of CAN communication with controller

Normal operation: Green LED

 

MTBF (Telcordia SR-332 Iss.I method III (a))

>350 000 (@ Tambient  : 25 °C)

Operating temp. (5-95% RH n.cond. hum.)

-40 to + 75°C [-40 to +167°F]

Max output power de-rates above temp / to

45°C [113°F] / 1200W @ 75°C[167°F]

Storage temperature

-40 to +85°C (-40 to +185°F),  humidity 0 - 99% RH non-condensing

Dimensions[WxHxD] / Weight

109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.950 kg (4.3lbs)

DESIGN STANDARDS

 

Electrical safety

EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013 UL 60950-1:2011

EMC

EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011,

IEC 61000-6-5: 2015, ETSI EN 300 386:2.1.1

Marine

DNVGL-CG-03392)

Environment

ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)

2011/65/EU (RoHS) & 2012/19/EU (WEEE)

Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other

operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised

OVS setting from controller select mode: OVS≤59.5V = 48V mode (42-58V), 59.5V<OVS<70.85 = 48V NiCad mode (39.9-66V) and OVS≥70.85V = 60V mode (52.5-72V). W hen de-energized module will return to 48V mode.

Only valid for part number 241115.705M

 


Send Inquiry

Product Alert

Subscribe to your interested keywords. We will send freely the latest and hottest products to your Inbox. Don't miss any trade information.

版权所有 © 宁波全贸信息技术有限公司 浙ICP备12012821号-1 浙B2-20200628