1 / 1
Model No. : | ZTD |
---|---|
Brand Name : | DDTOP |
Product description
DLC3010 tank level sensor |
Power supply: | 12~30V DC; the controller has reverse polarity protection.(when HART is communicating, the voltage of controller ≥17.75V DC) |
Output signal | 4~20 mA DC (Positive direction – the increase of level, interface, or density make output increase; Negative direction – the increase of level, interface, or density make output decrease.) |
Measuring range: | 300mm—2500mm (can also over range) |
Nominal pressure | ≤42.0Mpa |
Nominal diameter | DN40 or as customers’ request |
Ambient temperature | –40ºC to +80ºC (when ≤–30ºC, no LCD display) |
Operating temperature | –70ºC to +400ºC |
Measuring accuracy | 0.5% |
Influence from power supply | When the voltage of the power supply varies between min. and max. ,the output change is within<±0.2%. of the full scale. |
LCD display | Output current signal,process variable,process temperature,percentage range,rotation angle of torque tube. |
Medium density difference | ≥0.08g/cm³ |
Material of torque tube | Standard configuration Inconel 600,or Monel, HasetlloyC-276 |
Wetted material | 304,316L or as customers’ request |
Flange standard | HG/T20592-2009,HG/T20615-2009 or as customers’ request |
Power entry | Two NPT 1/2 (female thread) or as customers’ request |
Explosion-proof | Explosion isolation ExdⅡCT6, Intrinsically safe ExiaⅡCT6 |
Protection grade | IP66 |
Alarm jumper | For the self-diagnosis to the inaccuracy failure of the process variables (for example, the electronic module failure). Configure the process variables of high and low alarms. |
Send your inquiry to this supplier