Model No. : | BS-30W |
---|
Product description
engine brand | Ricardo WEICHAI |
---|---|
Frequency | 50hz |
Fuel | Diesel |
Rate | 1500-2000 |
Output Type | AC Three Phase |
Maximum Power | 10-30 |
Rated Current | 50-70 |
Rated Voltage | 400V |
Model | Prime KVA/KW | Engine Model | BOSS Alternator(dynamotor) |
BS-W10 | 10KVA /8KW | 2100D | STC-8/TFW-8/BCI164B |
BS-W12 | 12KVA/9.6KW | 2100D | STC-10/TFW-10/BCI164C |
BS-W15 | 15KVA/12KW | 2105D | STC-12/TFW-12/BCI164D |
BS-W20 | 20KVA/16KW | 495D | STC-16/TFW-16/BCI184E |
BS-W25 | 25KVA/20KW | K4100D | STC-20/TFW-20/BCI184F |
BS-W30 | 30KVA/24KW | K4100D | STC-24/TFW-24/BCI184G |
BS-W40 | 40KVA/32KW | K4100ZD | STC-32/TFW-32/BCI184H |
BS-W50 | 50KVA/40KW | R4105ZD | STC-40/TFW-40/UCI224D |
BS-W60 | 60KVA/48KW | R4105AZD | STC-48/TFW-48/UCI224E |
BS-W70 | 70KVA/56KW | R4105AZLD | STC-56/TFW-56/UCI224F |
BS-W84 | 84KVA/67KW | R6105ZD | TFW-67/UCI224G |
BS-W90 | 90KVA/72KW | R6105AZD | TFW-72/UCI274C |
BS-W110 | 110KVA/88KW | R6105AZLD | TFW-88/UCI274D |
BS-W132 | 132KVA/106KW | R6105IZLD | TFW-106/UCI274E |
BS-W150 | 150KVA/120KW | R6113AZD | TFW-120/UCI274F |
Genset Specifications:
1) Output range: 10-184kw
2) Engine model: Ricardo WEICHAI
3) Alternator model: ST/STC Series Brush alternator/Brushless with AVR copy stamford alternator
4) Water-cooled
5) 8hrs operation base tank
6) Key start / auto start
7) Sound-proof / weather-proof canopy is optional
8) 230 / 400V AC, 50Hz / 60Hz, 0.8pF three-phase and four wires alternating current output
9) Frequency: <3%
10) Frequency at stable state: <0.5%
11) Frequency deviation at instantaneous state: ≤+10%
12) Frequency return time: ≤3s
13) Voltage deviation at stable state: ≤±1%
14) Voltage deviation at instantaneous state: ≤+20%
15) Voltage return time: ≤4s
16) Voltage modulation: ≤0.3%
17) Standard configuration of gensets:
a) Engine: WEICHAI diesel engine
b) Engine type: water-cooled, in line four-stoke, Humit cylinder liner, direct injection
c) Alternator: brushless
18) Control system:
a) Automatic alarm system: the unit has the acousto-optics alarm
system and arrestor for any situation as the start defeat, the water
is over temperature, the oil pulls down, over speed, over load and
over current
b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers
19) Starting system: DC alternator is used to start engine
20) Short circuit protection: MCCB air switch
Payment Terms | L/C, T/T |
---|---|
Minimum Order | 1 |
Lead Time / Delivery Time | 30 Day(s) |
Sample Available | YES |
Delivery Details | 30% down payment and the rest should be cleared before delivery or upon copy of B/L received, or L/C. |