1 / 2
Model No. : | XPC series high frequency type |
---|---|
Brand Name : | EVERON, JFY or OEM |
Product description
MODEL | XPC 3110L | XPC 3115L | XPC 3120L |
Rated Power | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW |
INPUT | |||
Phase | 3W+N+G | ||
Input Voltage | (207-475)VAC | ||
Input Frequency | (46-54)Hz | ||
Input PF | >0.95 | ||
Bypass voltage | (302-437)VAC | ||
OUTPUT | |||
Output Voltage | 220VAC±1% | ||
Output Power Factor | 0.8 | ||
Output Frequency | Normal mode:same with utility power Battery mode:49.9~50.1Hz | ||
THD | THD<3% (linear load);THD<5% (non-linear load) | ||
Transfer Time | Normal to battery mode: 0ms Bypass mode to normal : 0ms | ||
Overload Capability | load≤105±5%:normally run;normal mode,turn to normal mode after overload disappearing 105±5%<load≤125±5%:60s 125%≤load≤150±5%:30s;>150% 0.1s | ||
BATTERY | |||
Voltage | 192Vdc | ||
Charging voltage | 220Vdc | ||
Overvoltage | 230Vdc | ||
Charging Current | 2A/4A(L type) | ||
SYSTEM | |||
Efficiency | >92% | ||
Communication | LCD display+RS-232 + Intelligent slot | ||
Restart Function | After turning off due to cut off voltage of battery, UPS will restart when voltage is in (302~437Vac) and frequency is in (47~53Hz). | ||
Noise (1m front) | <45dBA | <50dBA | |
Operation Temperature | 0°C to 40°C | ||
Humidity | 0~95% non-condensing | ||
Storage Temperature | -40°C to 50°C | ||
Altitude | 1000m | ||
Dimension(WXDXH) | 248×500×616 | ||
Weight(kg) | 27 | 35 | 35 |
Specification is subject to change without prior notice. |
Send your inquiry to this supplier