Baykee three phase high frequency true online solar ups HTT Series Brief BAYKEE HTT series UPS, adopt double conversion online type, which is an optimum design for all power failure. This design can effectively protect the loads from surges, meanwhile, ensure output stability, accuracy, reliability power to the loads. This series products adopt all digital control technology, can reach parallel redundancy function, to provide our customer more flexible, future expansion and safety guarantee. Features: Three phase input& output true online Double DSP+double CPLD all digital accurate operation control Input power factor up to 0.99, system efficiency>96% Input THDi<5%, output voltage regulation accuracy < +/-1% 200V-482V wide input range, all loads compatible Supper Over load capacity and short circuit protection Digital parallel redundancy tech,multi-parallel, full reliability Three stage charging, battery each set numbers 30~50 units optional (even) external battery life Modular design, average maintenance 10 min EPO function Application: IDC, financial, computer room, telecom, manufacturer, government project, transportation, medical and commercial use etc.. technical parameters HTT Series solar ups
Model | HTT-10K | HTT-15K | HTT-20K |
Capacity (kva/kw) | 10kva/8kw | 15kva/12kw | 20kva/16kw |
Input | |
Rated Voltage | 3*380V (3Ph+N) |
Voltage Range | +15% or -20% |
Frequency | 50Hz/60Hz+-5Hz |
Input Current Hormonic Distortion (THDi) | <1.5% @100% Load <2.5% @ 50% Load <6.0% @ 10% Load |
Limit Current | Overload: PEC limit current ( Battery charge ) |
Power Factor | 1.0 |
Inverter | |
Rated voltage | 3*380V (3Ph+N) |
Accuracy | Steady State:+-1%, Transient State:+-2% ( Load: 100-0-100% ) |
Frequency | Lock Bypass: 50Hz/60Hz+-5Hz, no input: +-0.05% |
Max. Phase-locked Speed | 10hz/s |
Output Waveform | Pure Sine Wave |
Output Voltage Hormonic Distortion (THDv) | <0.5% (linear load), <1.5% (nolinear load) |
Phase Deviation | 120º ±1% (balance load) 120º ±2% (above 50% unbalance load) |
Dynamic Response time | 10ms,recover to 98% of rated voltage 98% |
Overload time | 125% for 10 min., 150% for 60 s |
Crest Factor | 3.4 : 1 |
Output Load Power Factor | Lag of 0.7 to 0.7 ahead |
output voltage unbalance degree @100% unbalance load | <1% |
Current Limiting | overload,short circuit,Current value limit,high crest power factor, Peak current limit |
Static Bypass | |
Style | Static Bypass Switch |
Voltage | 3x380V (3 phase+N) |
Frequency | 50/60hz |
Efficiency (mains model) | 91% |
Specification | |
Size (L*W*H) mm | 700 x 450 x 1100 |
Weight (not includes battery) | 110 |
FAQ Trade Terms: Payment: T/T; 30% deposits; 70% balance before deliverying. Delivery Time: 10-15 days MOQ: 1pcs Package Informations: Why Choose us? We are China Leading UPS & Off-grid Solar System Manufacturer. Alibaba Assessed 4 years Gold Supplier. Inspected by the Inspection Institution of Bureau Veritas Certification. 100% QC inspection Before Shipmeng. Best Quality & Best Service with Competitive price. How to Contact Us? Send your Inquiry Details in the Below, Click "Send" Now!