MODEL | MP3100 |
Capacity | 120KVA |
Power Watt | 96KW |
Working Principle | Low Freuqency Transformer Based True On Line-Double Conversion |
RECTIFIER (INPUT) | |
Phase | Three Phase |
Input Power Factor | Standard > 0.9 ( 6pulse Rectifier+Filter ), Optional >0.96 ( 12pulse Rectifier+Filter) |
Input Voltage Range | 220/380VAC (230V/400VAC or 240V/415VAC)±25% 3P+N+PE |
Input Frequency Range | 50Hz±10% / 60Hz±10% (Selectable) |
Output Ripple | <2% |
Soft Start | 0~100% 5sec |
BATTERY | |
Type | VRLA/AGM/Gel, optional Lithium Battery |
Battery Capacity | 7~999AH settable ( Choose Battery Capacity according to Back-up Time ) |
Quantity | 30units 12V or 180units 2V batteries (Nominal Voltage 360VDC) |
Temperature | 20ºC~25ºC (For Maximum Efficiency) |
INVERTER (OUTPUT) | |
Phase | Single Phase |
Rated Voltage | Rated Capacity*0.9 |
Nominal Voltage | 220VAC (230VAC or 240VAC), 1P + N optional 110V(120V or 277V ) |
Output Voltage Regulated Accuracy | ±1 %( Stable load), ±3%( fluctuant load) |
Output Frequency Range | 50Hz 60Hz<±0.5% ( Asynchronous ) |
Crest Factor | > 3:1 |
Output Total Harmonic Distortion (THD) | Pure Sine Wave, Linear Load < 3%, Non-Linear Load<5% |
Dynamic Characteristics | Instant voltage<±5% ( from 0 to100% ), Instant recover time<10ms |
Unbalanced Load Voltage | < ± 5% |
Overload Capacity | At 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S |
Inverter Efficiency | >93% ( full load ) |
BYPASS | |
Phase | Single Phase |
By-pass Input Voltage | 220/380VAC (230V/400VAC or 240V/415VAC) optional 110V(120V or 277V ) |
By-pass Output Voltage | 220VAC (230VAC or 240VAC) optional 110V(120V or 277V ) |
Transfer Time | 0ms( adopt static switch ) |
PROTECTION FUNCTION | |
Input Protection | Input voltage, frequency over limited protection, Phase fault, Phase lack |
Output Protection | Over current, short circuit, over voltage, low voltage |
Battery Protection | Over charge, over-discharge protection |
Temperature Protection | Environment over temperature protection, inverter over temperature protection |
Hardware Fault Protection | Assistant power abnormal, breaker cut off, breaker overload, |
GENERAL SYSTEM PARAMETERS | |
Working Environment | Temp: -10~40ºC, relative humidity: 30%~90%, Altitude<2000m |
Cooling Method | COMPULSIVE VENTILATION |
Communitation Interface | RS232/ RS485, optional dry contact, SNMP card ( for remote control via internet ) |
Parallel Operation | Tandem hot backup or parallel connection |
Auti-surge Capacity | 10/700μS, 5KV; 8/20μS, 20KA |
Protection Level | IP21 |
Safety Performance | Vin-n Vout-n 2000Vac, creepage<10mA , insulating resistance>2MΩ(500VDC) |
Noise (dB) | 55~60 |
Dimension (W*D*H) mm | 980*800*1800 |
Weight (Kg) | 720 |