72v dc to ac ups
72v dc to ac ups
72v dc to ac ups

1 / 1

72v dc to ac ups

Get Latest Price
Send Inquiry
Model No. : XPC series online ups
Brand Name : JFY or OEM

Product description

72v dc to ac ups     1, Features   > True onlin double conversion completely isolates the load from various grid faults and pollution > Digital control technology provides high performance and system reliability. > Advanced IGBT-based the latest rectifier and inverter technology, high input power factor and low output harmonic. > Extra-wide input voltage and frequency range adapts adverse gird environment, compatible with diesel generator. > Intelligent battery management directly checking and setting charge and setting charge and discharge of battery on LCD      extends battery life. > Direct DC cold start function offers emergency on UPS by battery without utility power > Large LCD display monitor various real-time information at a glance. > Multiple monitoring and alarm functions availbale with dry contact of common alarms and RS232 for remote monitoring and      SNMP card(optional) for web-based monitoring     2, Specifications  
MODEL XPC 1101 XPC 1101L XPC 1102 XPC 1102L XPC 1103 XPC 1103L
Rated Power 1KVA/800W 2KVA/1600W 3KVA/2400W
INPUT
Phase L+N
Input Voltage (110±5 to 296±5)VAC
Input Frequency (45±0.5 to 55±0.5)Hz
Input PF >0.98
Bypass voltage (80±5 to 264±5)VAC
OUTPUT
Output Voltage 220VAC(1±2%)
Output Power Factor 0.8
Output Frenqency 45Hz~55Hz, same with utility power; <45Hz and >55Hz, lock 50Hz
Battery mode
:50/60(1±0.2%)Hz
THD THD<3% (linear load);THD<5% (Non-linear)
Transfer Time Normal to battery mode: 0ms
Between Battery modeand normal mode: <4ms
Overload Capability 105±5%Load150±5%:30s to bypass;
>150±5%
:300ms to bypass;
BATTERY
Battery Voltage 36Vdc 72Vdc 96Vdc
Battery Type 7AH/12V× 3pcs 7AH/12V× 6pcs 7AH/12V× 8pcs
Backup Time (Full Load) >5min(depends on battery capacity for L type)
Charging Current 1A/3A,4A,5A,6A,7A setable(L type)
SYSTEM
Efficiency >92%
Communication RS-232 + Intelligent Slot
Restart After turing off due to cut off voltage of battery, UPS will restart 
when voltage is in (170±5~286±5Vac) and freqency is in (46~54Hz).
Noise (1m front) <45dBA <50dBA
Operation Temperature 0°C to 40°C
Humidity 0~95% non-condensing
Storage Temperature -40°C to 50°C
Altitude <1000m,>1000m derated1% per 100m
Dimension(W*D*H)mm 145x360x210 195x455x330
Weight(kg) 12 6.5 27 16 33 16
*  Specification is subject to change without prior notice.