10KW/48V diesel air-cooled DC charging generator for Telecom
10KW/48V diesel air-cooled DC charging generator for Telecom
10KW/48V diesel air-cooled DC charging generator for Telecom
10KW/48V diesel air-cooled DC charging generator for Telecom

1 / 2

10KW/48V diesel air-cooled DC charging generator for Telecom

Get Latest Price
Send Inquiry
Model No. : YH12000M48-200
Brand Name : YOHOU

Product description

10KW/48V diesel air-cooled DC charging generator Description  Application:  for telecom base station. In case of public utility power is off, the DC generator can charge batteries to communication device. Rotor :     is neodymium permanent magnet rotor; high magnetic energy  Stator:     100% copper wire and welding Cold-Roll silicon Steel Sheets. Engine:     Powered by KOHLERK diesel engine Warranty:  double cylinder 3 year global warranty.    
Model YH12000M48-200
Generator Excitation System permanent magnet generator 
DC output Voltage(V) 48V (rating voltage)
  53.5V(floating voltage)      
   56.4V(Equalized Charging )
DC output Current(A)  200A (Rated current )
(10A-210A continuously adjustable )
     100A(Equalized Charging)
110A  (rating voltage)
     105A (floating voltage)
DC output Power [kw/(r/min)]  11.28/3600
Power  (kW) 10kw/12kw
Engine Brand KOHLER  KD477-2
Type double cylinder, 4 stroke , force air cooled
Displacement(cm³) 954
Continuous Power[kw/(r/min)] 14/3600
Start electric start
Lubricating Lubricating oil type 10℃ Below (Winter)
SAE15W-40
Lubricating oil capacity(L)  3
Fuel 0# diesel(Summer)or -20# diesel(Winter)
Protection Fule consumption(g/kw.hr) ≤244
Environmental characteristics  70kPa~106kPa
40℃~+55℃
-55℃~+70℃
Protection characteristics  battery reverse connection protection,
timing shutdown protection,
grid supply auto-shutdown protection , 
engine preheating protection; 
 engine lubricating oil level alarm protection, 
over-voltage protection, 
over-current protection,
limit-current protection, 
short-circuit protection,
module over-heating protection
Fuel tank capacity(L) 28
Start  condition
(stationary automatic type )
Grid supply unavailable, 
batteries voltage value lower than lower limit voltage value 
Shutdown condition
(stationary automatic type )
 Gird supply available
batteries voltage value higher than upper limit voltage value, 
batteries charging current, 
Timing shutdown
  Continuous work tim(hour/ratedpower) 24
  Noise level 
[non-load~full-load[dB(A)]
82~90
  Dimensions(L×W×H) (mm) 1150×740×769
  Weight(net weight) ≤190kg
 