The Powerhouse
Higher yield due to work-sharing is achieved by linking the two powercircuits using the MIX™, concept, our optimised master-slave system. In the part-load range only one of the two power stage sets operates, while both work together at full-load. The advantages are a noticeable increase in yield with a simultaneous reduction in operating hours. As the input voltage range of the FRONIUS IG 60 has been expanded from the former 500 V to 530 V, longer module strings can be connected. Due to this improvement, the product name changed
From 'FRONIUS IG 60' to 'FRONIUS IG 60 HV''HV'stands for 'High Voltage'.
Features:
FRONIUS LC-Display
HF-Transformer
Module-Manager
FRONIUS MIX-Concept
Technical Data
FRONIUS IG 40 60 HV
Input Data
MPP voltage range 150 - 400 V 150 - 400 V
Max. Input voltage (at 1000 W/m2; - 10) 500 V 530 V
PV system output 3500 - 5500 Wp 4600 - 6700 Wp
Max. Input current 29.4 A 35.8 A
Output Data
Nominal output 3500 W 4600 W
Max. Power output 4100 W 5000 W
Max. Efficiency 94.3 % 94.3 %
Euro efficiency 93.5 % 93.5 %
Mains voltage /frequemcy 230 V / 50 Hz (60 Hz)
Distortion factor < 3.5 %
Power factor 1
Power consumption at night 0 W
General Data
Size l x w x h 610 x 344 x 220 mm (733 x 435 x 225 mm)
Weight 16 kg (20 kg)
Cooling controlled forced-air cooling
Protection class (housing) IP 21 (IP 45)
Ambient temperature range - 20...50
Permissible humidity 0...95 %
Protective Devices
DC insultion measurement Warning when Riso < 500k Ohm
Polarity reversal protection built-in
Behaviour on DC overload displacement of operating point